A fitting stamped IP44 failed the handover anyway. The face passed its splash test, yet the inspector pointed at the ceiling over the shower: Zone 1, within 2.25 m above the bath and inside the 0.6 m ring, where the shower head throws a directed jet instead of splash. If the room includes a shower, choose bathroom downlight zones first and the IP rating second — the front-IP44 MIST-P downlight for Zone 2 and dry ceilings and the fully sealed DAMP-P for jet zones below each cover one side of that line.
Bathroom Zones And The IP Each One Demands
Bathroom zones come from IEC 60364-7-701, applied in the UK through BS 7671:2018 Section 701. The zone decides the test the fitting must survive; the IP code from IEC 60529:2013 only names that test. Read the table by position, then match the fitting — never the reverse.
| Zone | Where it is | Minimum IP | Fitting to order |
|---|---|---|---|
| Zone 0 | Inside the bath or shower tray itself | IPX7, 12 V SELV only | No downlight — low-voltage tray lighting only |
| Zone 1 | Above the bath or shower to 2.25 m height | IPX4 minimum, IPX5 where cleaning jets are used | Sealed IP65 DAMP-P, 20/40-degree lens |
| Zone 2 | 0.6 m ring around Zone 1, plus 0.6 m around the basin | IPX4 | Front-IP44 MIST-P, 60-degree diffuse |
| Outside zones | Beyond Zone 2, including most bathroom ceilings | No IP requirement, 30 mA RCD on the circuit | MIST-P or dry-room DL02 by cutout size |
Common practice is one IP number for the whole bathroom. BS 7671:2018 Section 701 requires the rating to follow the position, and one number fails where the jet reaches. Hotels that hose down wet rooms during cleaning should treat Zone 1 as IPX5 and order the sealed housing — the front-IP44 face survives splash from IEC 60529:2013 testing and says nothing about a directed jet. Require the zone plan on the RFQ before the supplier counts fittings.
US Reading: Damp Location Versus Wet Location
American projects do not use Zones 0 to 2. NEC Article 410.10(D) keeps cord-connected and exposed-lamp fittings out of the tub and shower area, measured 900 mm horizontally and 2.5 m vertically from the rim or threshold, and UL 1598 divides the rest by mark: a bathroom ceiling outside the tub and shower zone carries a damp-location mark, while the shower zone itself must read suitable for wet locations. A front-IP44 downlight satisfies the damp ceiling; only a fully sealed IP65 downlight carries the shower. State the mark per room on the inquiry so the factory bins each zone separately.
Front IP44 Is Not Whole-Fitting IP44
The MIST-P seals its front ring to IP44 and breathes through its body at IP20 in the ceiling void. That split is deliberate: splash and humid air stay out of the optic chamber while the driver cools in dry plenum air. It also draws the boundary — never hose the face during cleaning, and never order the front-IP44 housing for a position the shower stream can reach. The fully sealed IP65 DAMP-P downlight for showers and soffits closes both face and body, so jet zones, open eaves and balcony ceilings take one fitting instead of a compromise.
- Splash stays out — sealed front ring passes the IEC 60529:2013 splash test from all directions.
- Steam stays out — humid air never reaches the optic chamber or the lens seat.
- Jets stay a DAMP-P job — direct streams need the fully sealed body, not a tighter trim.
Cutout Picks In 75, 95 And 120 mm
Both families share one optic platform across three housings, so the hole decides the SKU and the zone decides the family. Measure the hole, not the old trim, and keep one CCT per room on the order. For dry-area holes above 120 mm, the PURE-S DL02 2-8 inch family for dry ceilings continues the range inside the LED downlight family index for hotels and shops.
| Hole | Zone 2 and outside zones | Zone 1 shower jets | Light output |
|---|---|---|---|
| 75 mm | MIST-P small housing, 10 W | DAMP-P small housing, 10 W | 1300 lm at 130 lm/W, 60-degree or 20/40-degree |
| 95 mm | MIST-P middle housing, 18 W | DAMP-P middle housing, 15 W | 1950 to 2340 lm, Ra80, 3000/4000/6000K |
| 120 mm | MIST-P large housing, 30 W | DAMP-P large housing, 25 W | 3250 to 3900 lm with 9 or 8 trim colors |
Soffits And Balconies Follow The Same Line
A covered eave or balcony ceiling behaves like a damp location: wind-driven rain arrives as splash, so front-IP44 is the floor. An open eave with no cover above takes direct weather and follows the shower rule into fully sealed IP65. Condensation drains matter as much as the rating — slope the housing seat outward and leave the driver in dry void air instead of sealing it against a cold soffit board. Write covered or open per elevation on the RFQ; one word decides the family.
Three Callbacks That Repeat Every Year
- Hosed faces — cleaners pressure-wash the IP44 face and force water past the trim. Ban jet washing on front-IP44 ceilings in the handover file and specify DAMP-P wherever hosing is routine.
- Cooked drivers — installers bury the driver in loft insulation and halve its life with heat. Keep clearance around the driver and the void ventilated, then test before the ceiling closes.
- One CCT everywhere — a single 6000K order turns guest bathrooms clinical. State warm 3000K for bathrooms and neutral 4000K for corridors per room so each zone bins separately.
What To Write On The Order
- Zone per room — mark Zone 1, Zone 2 or outside zones on the reflected ceiling plan so counts compare.
- Hole per position — 75, 95 or 120 mm measured at the ceiling, not at the old trim.
- CCT per room — 3000K rest areas, 4000K work and corridor ceilings, one CCT per room.
- Cleaning regime — splash-wipe or hose-down; hose-down moves Zone 1 to sealed IP65.
- Spares per batch — spare drivers ship with each batch under the five-year warranty; samples leave in 7 working days and bulk in 15 to 25 working days.
FAQ
Conclusion
Mark the zone, measure the hole, then pick the family: Zone 2 and outside zones take front-IP44 MIST-P in 75, 95 or 120 mm, while shower jets, hose-down rooms and open eaves take sealed IP65 DAMP-P. We do not publish custom-optic IES files; standard 60-degree and 20/40-degree photometry ships on request with the zone-matched submittal. This guide covers the requirements in force at the time of writing — confirm the current edition of BS 7671 and NFPA 70 with your inspector before signing.
The zone decides the test and the hole decides the SKU — one IP number for the whole bathroom fails exactly where the jet reaches.
Sources
- According to the IP code and its IEC 60529 test definitions, IPX4 covers splashing water from all directions while IPX5 covers directed jets.
- The National Electrical Code tub and shower provisions keep unsuitable fittings out of the 900 mm by 2.5 m zone and divide the rest into damp and wet locations.
WHY BUYERS WORK WITH LOW CARBON TECLUX
About Low Carbon Teclux
Low Carbon Teclux Co., Ltd. has manufactured LED commercial lighting since 2010. As a factory-direct OEM/ODM manufacturer, we serve importers and distributors across Europe and Australia — from product selection and sample testing to mass production and delivery, one team covers engineering, manufacturing and sales.
Our Engineering Support
We help project buyers select the right fitting, optic and driver — not just compare prices. Send us your application, mounting height, target lux, dimming protocol and finish requirement, and our engineers will recommend a series, optic, driver basis and spare-parts plan for your RFQ. Where no standard fitting fits, we co-develop custom luminaires around your project — housing, optic, driver and finish engineered to your spec, from prototype to mass production.
REQUEST A QUOTECOMPANY PROFILE // DATA_SHEET
NAME
Low Carbon Teclux Co., Ltd.
BRAND NAME
Low-Carbon
BUSINESS TYPE
LED Lighting Manufacturer
SERVICE
Factory Direct / OEM / ODM
MAIN PRODUCTS
LED Track Lights, Linear Lights, Downlights, Outdoor Luminaires
CAPABILITY
Engineering, Manufacturing & Sales in One Team; Sample to Mass Production
CERTIFICATIONS
CE / FCC / RoHS / ISO9001
EXPORT REACH
Europe & Australia
Contents Table
Related Product

Need Help Selecting the Right Luminaire?
Tell us your application, mounting height and target lux — our engineers will recommend a fitting, optic and driver configuration, or co-develop a custom fitting when no standard model fits.
REQUEST A QUOTESend Message
Fill out the form and we will get back to you as soon as possible